3 CONDUCTOR
3 CONDUCTOR COPPER WIRE GUAGE SIZE
WATTS PER
FIXTURE
# of
FIXTURES
APPROX.
AMPS
#14 (m)
#14 (ft)
#12 (m)
#12 (ft)
#10 (m)
#10 (ft)
#8 (m)
#8 (ft)
75
2
0.7
770
3540
1200
3930
2000
6550
3070
10070
75
3
1.1
490
1610
760
2500
1270
4170
1950
6410
75
4
1.4
390
1270
600
1960
1000
3270
1540
5040
75
6
2.1
260
850
400
1310
670
2180
1020
3360
75
8
2.8
190
630
300
980
500
1640
770
2520
150
2
1.4
390
1270
600
1960
1000
3270
1540
5040
150
3
2
270
890
420
1380
700
2300
1080
3530
150
4
2.7
200
660
310
1020
520
1700
800
2610
150
6
4.1
130
430
200
670
340
1120
520
1720
150
8
5.5
100
320
150
500
250
830
490
1280
250
2
2.3
240
770
360
1200
610
1990
930
3070
250
3
3.4
160
520
250
810
410
1350
630
2070
250
4
4.5
120
390
190
610
310
1020
480
1570
250
6
6.8
75
250
120
400
210
670
320
1040
250
8
9.1
60
200
90
300
150
500
240
780
500
4
9.1
60
200
90
300
150
500
240
780
500
6
13.6
40
130
60
200
100
340
160
520
500
8
18.2
requires 2 runs of cable
2 runs of cable required at:
---
---
90
300
150
500
240
780
AquaMaster® recommends consulting a licensed electrician to properly size any underground cable from the main power source to our control panel. Please contact AquaMaster® if assistance is required.
Maximum Recommended Length from Fountain Lights to Control Panel for
Masters Series®, Classic Series and Celestial Fountains®
FEATURES 60Hz CABLE SIZING
  50Hz CABLE SIZING